Signal LED1
Signal LED2
Power contact
230 V
Power contact N
Power contact PE
Output 1
Output 2
230 V
N
PE
Top view
Contact assembly
Signal LED1
Signal LED2
Power contact
230 V
Power contact N
Power contact PE
Output 1
Output 2
230 V
N
PE
Top view
Contact assembly
KL2712, KL2722 | 2-channel triac output terminals 12…230 V AC
The KL2712 and KL2722 output terminals use a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 0.5 A (KL2712) or 1 A (KL2722). The KL2712 terminal has two independent outputs. Its signal state is indicated by means of light emitting diodes. The KL2722 has two mutually locked outputs. The terminals are most suitable for reverse motors.
| Technical data |
KL2712 | KS2712 |
KL2722 | KS2722 |
| Connection technology |
4-wire |
| Number of outputs |
2 x make contacts |
| Rated load voltage |
12…230 V AC |
| Load type |
ohmic, inductive |
| Output current |
max. 0.01…0.5 A continuous load per channel |
1 A (leakage current: typ. 0.8 mA, max. 1.5 mA) |
| Max. output current |
2 x 0.01…0.5 A |
1 x 1 A |
| Frequency range |
47…63 Hz |
| Surge voltage protection |
> 275 V AC |
| Peak current |
40 A (16 ms), 1.5 A (30 s) |
40 A (16 ms), 3 A (30 s) |
| Switch-on time |
0.1 ms |
0.1…10 ms, zero crossing |
| Switch-off time |
T/2 |
| Maximum residual voltage |
1.5 V |
| Electrical isolation |
500 V (K-bus/field voltage), 3,750 V AC (1 min.) |
| Leakage current |
typ. 0.8 mA, max. 1.5 mA (OFF state) |
| Current consumption power contacts |
only leakage and load current |
| Current consumpt. K-bus |
typ. 10 mA |
| Bit width in the process image |
2 outputs |
| Configuration |
no address or configuration setting |
| Special features |
reverse motors (blinds) |
| Weight |
approx. 55 g |
| Operating/storage temperature |
0…+55 °C/-25…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |
| Pluggable wiring |
for all KSxxxx Bus Terminals |
| Approvals |
CE, UL, Ex, GL |
CE, Ex, GL |
 |
 |
 |
| Special terminals |
|
| KL2722-0010 |
without reciprocal locking of the channels, total current 1 A |