The KL2284 output terminal switches loads in selectable polarity. This means that DC motors can be used in both directions of rotation. A polarity is switched with two output bits per channel. An interlock prevents simultaneous switching of both directions. Advanced power semiconductors enable safe and wear-free switching with minimum dimensions. The high starting and short-circuit currents of the KL2284 are comparable with a robust relay. The number of switching cycles is almost unlimited.
| Technical data | KL2284 | KS2284 |
|---|---|
| Connection technology | 2-wire |
| Number of outputs | 4 x H-bridge circuit |
| Rated load voltage | 0…24 V DC |
| Output current | 2 A on each channel |
| Breakdown voltage | 80 V |
| Peak current | 5 A (100 ms), < 50 A (10 ms) |
| Electrical isolation | 500 V (K-bus/field potential) |
| Switching on speed | typ. 235 ms, max. 300 ms |
| Switching off speed | typ. 30 ms, max. 50 ms |
| On-resistance | typ. 0.03 Ω |
| Current consumpt. K-bus | 100 mA |
| Bit width in the process image | 8 outputs |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals | CE |
![]() |
![]() |