The KL1809 and KL1819 digital input terminals acquire the binary control signals from the process level and transmit them, in an electrically isolated form, to the higher-level automation device. The Bus Terminals each contain 16 channels, whose signal states are displayed by LEDs. The terminals are particularly suitable for space-saving use in control cabinets. By using the single-conductor connection technique, a multi-channel sensor can be connected in the smallest space with a minimum amount of wiring. The power contacts are looped through.
For the KL1809 and KL1819 Bus Terminals, the reference ground for all inputs is the 0 V power contact. The versions have input filters with different speeds. The conductors can be connected without tools in the case of solid wires using a direct plug-in technique.
The HD Bus Terminals (High Density) with increased packing density feature 16 connection points in the housing of a 12 mm terminal block.
| Technical data | KL1809 | KL1819 |
|---|---|---|
| Connection technology | 1-wire | |
| Specification | EN 61131-2, type 1/3 | |
| Number of inputs | 16 | |
| Nominal voltage | 24 V DC (-15 %/+20 %) | |
| “0“ signal voltage | -3…+5 V (EN 61131-2, type 1/3) | |
| “1“ signal voltage | 11…30 V (EN 61131-2, type 3) | |
| Input filter | typ. 3.0 ms | typ. 0.2 ms |
| Input current | typ. 3 mA (EN 61131-2, type 3) | |
| Current consumpt. K-bus | typ. 20 mA | |
| Current consumption power contacts | typ. 4 mA + load | |
| Electrical isolation | 500 V (K-bus/field potential) | |
| Bit width in the process image | 16 inputs | |
| Configuration | no address or configuration setting | |
| Conductor types | solid wire, stranded wire and ferrule | |
| Conductor connection | solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver | |
| Rated cross-section | solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm² | |
| Weight | approx. 60 g | |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C | |
| Relative humidity | 95 %, no condensation | |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
| Protect. class/installation pos. | IP 20/variable (see documentation) | |
| Approvals | CE, UL, Ex | |
![]() |
![]() |
![]() |